DUAL SETPOINT RELAY OUTPUT
SPECIFICATIONS
Setpoint Output Cards: Six types of field installable cards
Response Time: 200 msec. max. to within 99% of final readout value
(digital filter and internal zero correction disabled) 700 msec. max.
(digital filter disabled, internal zero correction enabled)
PAXH only: 1 sec. max. to within 99% of final readout value (digital
filter disabled)
PAXT only: 200 msec. typ.; 700 msec max. (digital filter disabled)
PAXH Isolation For All Four Cards:
Isolation To Sensor Common: 1400 Vrms for 1 min.
Isolation To User Input Common: 500 Vrms for 1 min.
Dual Relay Card: PAXCDS10
Type: Two FORM-C relays
Isolation To Sensor & User Input Commons: 2000 Vrms for 1 min.
Contact Rating:
One Relay Energized: 5 amps @ 120/240 VAC or 28 VDC (resistive
load).
Total Current With Both Relays Energized not to exceed 5 amps
Life expectancy: 100 K cycles min. at full load rating. External RC
snubber extends relay life for operation with inductive loads
Quad Form A Relay Card: PAXCDS20
Type: Four FORM-A relays
Isolation To Sensor & User Input Commons: 2300 Vrms for 1 min.
Contact Rating:
One Relay Energized: 3 amps @ 250 VAC or 30 VDC (resistive load).
Total Current With All Four Relays Energized not to exceed 4 amps
Life Expectancy: 100 K cycles min. at full load rating. External RC
snubber extends relay life for operation with inductive loads
Quad Sinking Open Collector Card: PAXCDS30
Type: Four isolated sinking NPN transistors.
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Not Isolated from all other commons.
Rating: 100 mA max @ VSAT = 0.7 V max. VMAX = 30 V
Quad Sourcing Open Collector/SSR Drive Card: PAXCDS40
Type: Four isolated sourcing PNP transistors.
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Not Isolated from all other commons.
Rating:
Internal supply: 18/24 VDC (unit dependent) ± 10%, 30 mA max. total
all four outputs
External supply: 30 VDC max., 100 mA max each output
Dual Triac/Dual SSR Drive Card: PAXCDS50
Triac:
Type: Isolated, zero crossing detection
Voltage: 260 VAC max., 20 VAC min.
Max Load Current: 1 Amp @ 25°C
0.75 Amp @ 50°C
Total load current with both triacs ON not to exceed 1.5 Amps
Min Load Current: 5 mA
Off State Leakage Current: 1 mA max @ 60 Hz
Operating Frequency: 20-400 Hz
SSR Drive:
Type: Two isolated sourcing PNP Transistors.
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Not Isolated from all other commons.
Rating:
Output Voltage: 18/24 VDC (unit dependent) ± 10%, 30 mA max.
total both outputs
Quad Form C Relay Card: PAXCDS60
Type: Four FORM-C relays
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Contact Rating:
Rated Load: 3 Amp @ 30 VDC/125 VAC
Total Current With All Four Relays Energized not to exceed 4 amps
Life Expectancy: 100 K cycles min. at full load rating. External RC
snubber extends relay life for operation with inductive load
Reviews
There are no reviews yet.