P1-25/EA/SVB SECCIONADOR 3

SKU: MOE041097
In Stock
$1,845.88
In Stock
Add to Wishlist
Add to Wishlist
Add to Wishlist
Add to Wishlist
Compare
SKU: MOE041097 Categories: ,

P1-25/EA/SVB SECCIONADOR 3

General
Standards
IEC/EN 60947, VDE 0660, IEC/EN 60204, CSA, UL
Switch-disconnector according to IEC/EN 60947-3
NEMA12
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Open
-25 - +50 °C
Ambient temperature
Enclosed
-25 - +40 °C
Overvoltage category/pollution degree
III/3
Rated impulse withstand voltage [Uimp]
6000 V AC
Mechanical shock resistance
15 g
Mounting position
As required
Contacts
Mechanical variables
Number of poles
3 pole
Mechanical variables
Auxiliary contacts

0 N/O
Mechanical variables
Auxiliary contacts

0 N/C
Electrical characteristics
Rated operational voltage [Ue]
690 V AC
Electrical characteristics
Rated uninterrupted current [Iu]
25 A
Electrical characteristics
Note on rated uninterrupted current !u
Rated uninterrupted current Iu is specified for max. cross-section.
Load rating with intermittent operation, class 12
AB 25 % DF
2 x Ie
Load rating with intermittent operation, class 12
AB 40 % DF
1.6 x Ie
Load rating with intermittent operation, class 12
AB 60 % DF
1.3 x Ie
Short-circuit rating
Fuse
25 A gG/gL
Rated short-time withstand current (1 s current) [Icw ]
640 Arms
Note on rated short-time withstand current lcw
Current for a time of 1 second
Rated conditional short-circuit current [Iq]
50 kA
Switching capacity
cos ϕ rated making capacity as per IEC 60947-3
240 A
Rated breaking capacity cos ϕ to IEC 60947-3
230 V
190 A
Rated breaking capacity cos ϕ to IEC 60947-3
400/415 V
150 A
Rated breaking capacity cos ϕ to IEC 60947-3
500 V
170 A
Rated breaking capacity cos ϕ to IEC 60947-3
690 V
150 A
Safe isolation to EN 61140
between the contacts
440 V AC
Safe isolation to EN 61140
Current heat loss per contact at Ie
1.1 W
Lifespan, mechanical [Operations]
> 0.3 x 106
Maximum operating frequency [Operations/h]
1200
AC
AC-3
Rating, motor load switch [P]
220 V 230 V [P]
5.5 kW
AC
AC-3
Rating, motor load switch [P]
400 V 415 V [P]
7.5 kW
AC
AC-3
Rating, motor load switch [P]
500 V [P]
7.5 kW
AC
AC-3
Rating, motor load switch [P]
690 V [P]
7.5 kW
AC
AC-3
Rated operational current motor load switch
230 V [Ie]
19.6 A
AC
AC-3
Rated operational current motor load switch
400V 415 V [Ie]
15.2 A
AC
AC-3
Rated operational current motor load switch
500 V [Ie ]
12.1 A
AC
AC-3
Rated operational current motor load switch
690 V [Ie]
8.8 A
AC
AC-23A
Motor rating AC-23A, 50 - 60 Hz [P]
230 V [P]
5.5 kW
AC
AC-23A
Motor rating AC-23A, 50 - 60 Hz [P]
400 V 415 V [P]
11 kW
AC
AC-23A
Motor rating AC-23A, 50 - 60 Hz [P]
500 V [P]
11 kW
AC
AC-23A
Motor rating AC-23A, 50 - 60 Hz [P]
690 V [P]
11 kW
AC
AC-23A
Rated operational current motor load switch
230 V [Ie]
25 A
AC
AC-23A
Rated operational current motor load switch
400 V 415 V [Ie]
25 A
AC
AC-23A
Rated operational current motor load switch
500 V [Ie]
17.4 A
AC
AC-23A
Rated operational current motor load switch
690 V [Ie]
12.6 A
DC
DC-1, Load-break switches L/R = 1 ms
Rated operational current [Ie]
25 A
DC
DC-1, Load-break switches L/R = 1 ms
Voltage per contact pair in series
60 V
DC
DC-23A, motor load switch L/R = 15 ms
24 V
Rated operational current [Ie]
25 A
DC
DC-23A, motor load switch L/R = 15 ms
24 V
Contacts
1 Quantity
DC
DC-23A, motor load switch L/R = 15 ms
48 V
Rated operational current [Ie]
25 A
DC
DC-23A, motor load switch L/R = 15 ms
48 V
Contacts
2 Quantity
DC
DC-23A, motor load switch L/R = 15 ms
60 V
Rated operational current [Ie]
25 A
DC
DC-23A, motor load switch L/R = 15 ms
60 V
Contacts
2 Quantity
DC
DC-23A, motor load switch L/R = 15 ms
120 V
Rated operational current [Ie]
12 A
DC
DC-23A, motor load switch L/R = 15 ms
120 V
Contacts
3 Quantity
Control circuit reliability at 24 V DC, 10 mA [Fault probability]
< 10-5,< 1 failure in 100,000 switching operations HF
Terminal capacities
Solid or stranded
1 x (1,5 - 6)
2 x (1,5 - 6) mm2
Flexible with ferrules to DIN 46228
1 x (1 - 4)
2 x (1 - 4) mm2
Terminal screw
M4
Tightening torque for terminal screw
1.6 Nm
Technical safety parameters:
Notes
B10d values as per EN ISO 13849-1, table C1
Rating data for approved types
Contacts
Rated operational voltage [Ue]
600 V AC
Contacts
Rated uninterrupted current max.
Main conducting paths
General use
20 A
Contacts
Rated uninterrupted current max.
Auxiliary contacts
General Use [IU]
10 A
Contacts
Rated uninterrupted current max.
Auxiliary contacts
Pilot Duty
A 600
P 600
Switching capacity
Maximum motor rating
Single-phase
120 V AC
1 HP
Switching capacity
Maximum motor rating
Single-phase
200 V AC
2 HP
Switching capacity
Maximum motor rating
Single-phase
240 V AC
3 HP
Switching capacity
Maximum motor rating
Three-phase
200 V AC
3 HP
Switching capacity
Maximum motor rating
Three-phase
240 V AC
5 HP
Switching capacity
Maximum motor rating
Three-phase
480 V AC
10 HP
Switching capacity
Maximum motor rating
Three-phase
600 V AC
15 HP
Short Circuit Current Rating
Basic Rating
5 kA
Short Circuit Current Rating
max. Fuse
110 A
Short Circuit Current Rating
High fault rating
10 kA
Short Circuit Current Rating
max. Fuse
50, Class J A
Terminal capacity
Solid or flexible conductor with ferrule
14 - 8 AWG
Terminal capacity
Terminal screw
M4
Terminal capacity
Tightening torque
14.1 lb-in
DESIGN VERIFICATION AS PER IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation [In]
25 A
Heat dissipation per pole, current-dependent [Pvid]
1.1 W
Equipment heat dissipation, current-dependent [Pvid]
0 W
Static heat dissipation, non-current-dependent [Pvs]
0 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+50 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts
10.2.4 Resistance to ultra-violet (UV) radiation
UV resistance only in connection with protective shield.
10.2 Strength of materials and parts
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Reviews

There are no reviews yet.

Be the first to review “P1-25/EA/SVB SECCIONADOR 3”

Tu dirección de correo electrónico no será publicada. Los campos obligatorios están marcados con *

Select the fields to be shown. Others will be hidden. Drag and drop to rearrange the order.
  • Image
  • SKU
  • Rating
  • Price
  • Stock
  • Availability
  • Add to cart
  • Description
  • Content
  • Weight
  • Dimensions
  • Additional information
  • Attributes
  • Custom attributes
  • Custom fields
Click outside to hide the compare bar
Compare